The Fyre-Tec fixed lite windows offer 3/4- or 1-hour rated protection. They are ideal for inclusion in rated corridors or exterior walls where it is essential to provide natural light but ventilation is not required. The fixed lites also may be combined with an operable Fyre-Tec window to provide a larger opening with greater daylight area.

Options include 1-hour ratings, premium non-wire glass glazing, custom colors.


SPECIFICATIONS
Series 950
Fixed Lite UL Fire Rated Steel Window

Guide Specification for Use when Completing

SECTION 08505 - METAL WINDOWS

STEEL WINDOWS


PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)


ASTM A 569 (1991a; R 1993) Steel, Carbon (0.15 Maximum, Percent), Hot-Rolled Sheet and Strip Commercial Quality

ASTM A 653 (1994) Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B 633 (1985; R 1994) Electrodeposited Coatings of Zinc on Iron and Steel

ASTM B 766 (1986; R 1993) Electrodeposited Coatings of Cadmium


ASTM E 163 Fire Tests of Window Assemblies

ASTM E 283 (1991) Determining the Rate of Air Leakage through Exterior Windows, Curtain Walls, and Doors Under Specifies Pressure Differences Across the Specimen

ASTM E 330 (1990) Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference

ASTM E 547 (1993) Water Penetration of Exterior Windows, Curtain Walls, and Doors by Cyclic Static Air Pressure Differential


AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)

ASME B18.6.3 (1972; R 1991) Machine Screws and Machine Screw Nuts

ASME B18.6.4 (1981; R 1991) Thread Forming and Thread Cutting Tapping Screws and Metallic Drive Screws (Inch Series)

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 80 (1992) Fire Doors and Windows

NFPA 101 (1994) Safety to Life from Fire in Buildings and Structures

UNDERWRITERS LABORATORIES INC.

UL9 Fire Tests of Window Assemblies
File No. R13157 D.V. Fyre-Tec Classification


1.2 WINDOW PERFORMANCE

Steel windows shall be designed to meet the following performance requirements, and shall be of the type and size indicated. Fire-rated windows shall bear the Underwriters Laboratories, Inc. label including the manufacturer’s file number for the indicated rating.

1.2.1 Fire Resistance

Fire resistance shall meet requirements established by ASTM E 163 and as tested and classified by Underwriters Laboratories Inc, in accordance with UL-9. Products shall meet the requirements of Underwriters Laboratories Inc. The Listing Mark of UL on the product will be accepted as evidence of compliance.

A. Rated protected openings specified as _-hour shall be glazed with rated wire glass

B. Rated protected openings specified as 1-hour shall be glazed with clear ceramic glass (non-wire) with a minimum 1-hour rating.

1.2.2 Life Safety Criteria

Windows shall conform to NFPA 101 Life Safety Code when rescue and/or second means of escape are indicated.

1.3 SUBMITTALS

A. Manufacturer’s descriptive data and catalog cut sheets.


B. Drawings indicating elevations of windows, rough-opening dimensions for each type and size of windows, full-size sections, thickness of metal, fastenings, methods of installation and anchorage, connections with other work, type of wall construction, size and spacing of anchors, method of glazing, types and locations of operating hardware, mullion details and window schedules showing locations of each window type and indicting compliance with fire safety code, where required.

C. Manufacturer’s preprinted installation instructions and cleaning instructions.


D. Certificates stating that the steel windows conform to requirements of this section.

E. Manufacturer’s standard color samples of painted finishes.


1.4 QUALIFICATION

Window manufacturer shall specialize in designing and manufacturing the type of steel windows specified, and shall have a minimum of 5 years of documented successful experience. Manufacturer shall have the facilities capable of meeting contract requirements, single-source responsibility and warranty.


1.5 DELIVERY AND STORAGE

Steel windows shall be delivered to project site and stored in accordance with manufacturer’s recommendations.


PART 2 PRODUCTS

2.1 GENERAL

2.1.1 Manufacturer: Subject to compliance with Contract Documents and specifications, provide one of the following:

A: Series 950 Fixed Lite Window as manufactured by D.V. Fyre-Tec, Wayne, NE 68787 (800-377-3261).

B: Architect approved equal.

2.2 MATERIALS

2.2.1 Steel Frames

Steel frames shall be fabricated from roll-formed galvanized lock-forming quality steel per ASTM A 527. Frame corners shall mitered and welded. Integral munton shall be galvanized roll-formed material fitted and welded.

2.2.2 Formed Component Parts

Formed component parts shall be hot-rolled sheet steel conforming to ASTM A 569, commercial quality with a minimum of 0.15 percent carbon. Sheet steel shall be zinc coated (galvanized) by the hot-dip process in accordance with ASTM A 653 or ASTM A 924.

2.2.3 Screws and Bolts

Screws and bolts shall conform to ASTM B 766, ASME B18.6.3 and ASME B18.6.4.

2.3 STEEL WINDOW TYPES

Steel windows shall be designed for inside field glazing, and for glass types scheduled on drawings or otherwise specified. Units shall be complete with glass and glazing provisions to meet requirements of paragraph WINDOW PERFORMANCE. Glazing material shall be compatible with steel, and shall not require painting.


2.3.1 Fixed Windows

Steel fixed windows shall be commercial window type, non-operable glazed frame, complete with provisions for reglazing in the field.


2.3.2 Fire-Rated Windows

Fire-rated windows shall conform to UL-9 and shall be labeled with a 3/4 or 1 hour fire-test rating as specified in the window schedule. Units shall be designed and fabricated to meet glass sizes, window sizes, and opening dimensions established by NFPA 80. Hardware shall conform to NFPA 80 requirements.

2.4 ACCESSORIES


2.4.1 Fasteners

Fastening devices shall be window manufacturer’s design made from non-magnetic stainless steel, cadmium-plated steel, zinc-plated steel, nickel/chrome-plated steel or magnetic stainless steel

2.4.2 Window Anchors

Anchors for installing windows shall be stainless steel or hot-dip zinc coated steel conforming to ASTM A 123.

2.5 FINISHES

2.5.1 Prime Coat

Steel windows, fins, mullions, cover plates and associated parts shall be cleaned, pre-treated with iron phosphate and factory painted manufacturer’s standard primer coat in a dry film thickness of not less than 0.025 mm (1.0 mil).

OR Finish Coat

Steel windows, fins, mullions, cover plates and associated parts shall be cleaned, pre-treated with iron phosphate and factory powder coated and cured with a manufacturer’s standard color in a dry film thickness of not less than 0.050 mm (2.0 mil).

OR Finish Coat

Steel windows, fins, mullions, cover plates and associated parts shall be cleaned, pre-treated with iron phosphate and factory coated with baked alkyd enamel with a manufacturer’s standard color in a dry film thickness of not less than 0.050 mm (2.0 mil).

PART 3 EXECUTION

3.1 INSTALLATION

Steel windows shall be installed in accordance with approved shop drawings and manufacturer’s approved recommendations. Fire-rated windows shall be installed in compliance with NFPA 80 and NFPA 101. Steel surfaces in close proximity with masonry, concrete, wood, and dissimilar metals other than stainless steel, zinc, cadmium, or small areas of white bronze shall be protected from direct contact. The completed window installation shall be watertight. Fire-rated windows shall be glazed in accordance with NFPA 80.

3.2 CLEANING


3.2.2 Cleaning

Steel window finish and glass shall be cleaned on interior and exterior sides in accordance with window manufacturer’s recommendation. Alkaline or abrasive agents shall not be used.